Sizing 24VDC Power Supplies & Contactors for DIN-Rail Relays

Use an eight-channel DIN-rail relay example to size a 24VDC supply for holding and pickup current, check derating, and choose contactors.

By DIN Relay Guide Editorial · · 3 min read

Size the 24 VDC supply for the largest steady load and the highest startup load when coils pull in together. Compare the holding load with the supply’s continuous rating at the enclosure temperature. If the supply has a peak rating, check that it covers the startup load for the time it lasts. Choose each contactor’s coil for the control circuit and its main poles for the load voltage, current and switching duty. Power supply sizing · Example contactor ratings

Calculate holding and pickup current

List the relay inputs, contactor coils and any controller, sensors or other equipment fed by the same 24 VDC supply. Use each device’s published maximum current where available. If a 24 VDC coil is specified in watts, divide those watts by 24 to estimate its current at nominal voltage. Maple Systems sizing guide

  • Holding current. Add the current of devices already powered and the hold-in current of every coil that can remain energized together.
  • Pickup current. For each possible start, add the current already on the supply and the inrush current of coils that can start together. Use hold-in current for coils already energized, and count each coil once.

Worked example for eight channels

Assume eight relay outputs each switch one Schneider Electric contactor coil from the same 24 VDC supply. All eight can stay on, and all eight can start together. Calculate the coil subtotals from the published contactor coil powers at 20 °C. Schneider LC1D09BD · Schneider LC1D50ABD

Load on the 24 VDC supplyAll channels holdingAll channels picking up
Relay inputs and other devices on the same supplyAdd current in the holding caseAdd current in the pickup case
4 LC1D09BD coils, 5.4 W each for hold-in and inrush (at 20 °C)4 × 5.4 W ÷ 24 V = 0.900 A4 × 5.4 W ÷ 24 V = 0.900 A
4 LC1D50ABD coils, 7.4 W holding and 19 W inrush each (at 20 °C)4 × 7.4 W ÷ 24 V ≈ 1.233 A4 × 19 W ÷ 24 V ≈ 3.167 A
Calculated contactor coil subtotal2.13 A4.07 A

In this example, consider one LC1D50ABD picking up while the other seven coils hold. Replace that coil’s holding current with its pickup current. The coil subtotal becomes 0.900 A + 1.233 A + (19 W − 7.4 W) ÷ 24 V ≈ 2.62 A. Use the simultaneous figure if the channels can start together at power-up.

Check continuous capacity and timed boost

Add the relay inputs and other 24 VDC loads to each coil subtotal before comparing the totals. Use the supply’s derating curve to find its continuous output at the worst-case enclosure temperature. The holding total must fit within that output. Maple Systems sizing guide

If the pickup total exceeds continuous output, check the supply’s peak current and the time it can sustain that current. Confirm that the supply is rated for the available AC input voltage. Maple Systems’ Economical models must cover the pickup total with their rated current. Maple Systems sizing guide

Check coil current and suppression

  • Coil current. The example LC1D50ABD draws about 0.79 A at pickup and 0.31 A holding, calculated at 24 V from the 20 °C coil specs. Schneider LC1D50ABD coil data
  • Coil suppression. Check whether the contactor coil has built-in suppression. Both example contactors list a built-in bidirectional diode suppressor. LC1D09BD coil data · LC1D50ABD coil data

Select the contactor coil and main poles

  • Coil. Specify 24 VDC for this control supply. Check the control circuit voltage and use the exact coil variant’s inrush and hold-in data in the current budget. Example coil data
  • Main poles. Match the load’s voltage and current to the contactor’s rated operational voltage and current for the applicable utilization category. Check the pole arrangement under pole contact composition. Both example contactors have three normally open main poles. Schneider LC1D09BD · Schneider LC1D50ABD
  • Duty. Check the selected model’s application and utilization category. Schneider lists the example contactors for motor control under AC-3/AC-3e. Check the maximum operating rate at the stated temperature. Schneider LC1D09BD · Schneider LC1D50ABD

Evidence and limits. The calculations are based on the linked product data and sizing guidance checked on November 26, 2026. This guide is not based on hands-on testing.

Sources

  1. Maple Systems DIN-rail power supply sizing guide
  2. Schneider Electric LC1D09BD contactor technical data
  3. Schneider Electric LC1D50ABD contactor technical data