<?xml version="1.0" encoding="UTF-8"?><rss version="2.0" xmlns:content="http://purl.org/rss/1.0/modules/content/" xmlns:atom="http://www.w3.org/2005/Atom"><channel><title>DIN Relay Guide: DIN Rail Ethernet Relay Boards</title><description>Plain guides to DIN rail Ethernet relay boards, built from published official documentation.</description><link>https://dinrelayguide.com/</link><language>en</language><atom:link href="https://dinrelayguide.com/rss.xml" rel="self" type="application/rss+xml"/><item><title>Dry vs Wet Contacts on Opto-Isolated DIN Relay Inputs</title><link>https://dinrelayguide.com/posts/dry-contact-wet-contact-opto-isolated-inputs-wiring/</link><guid isPermaLink="true">https://dinrelayguide.com/posts/dry-contact-wet-contact-opto-isolated-inputs-wiring/</guid><description>Wire dry switches and powered NPN or PNP sensors to opto-isolated DIN relay inputs. Match the input mode, common terminal, and DC voltage range.</description><pubDate>Thu, 26 Nov 2026 00:00:00 GMT</pubDate><content:encoded>&lt;p&gt;A dry-contact input senses a switch closure. A wet-contact input senses whether voltage is applied. For a DIN relay board, match the field device to the board’s dry or wet input mode before connecting it. &lt;a href=&quot;https://wiki.wirenboard.com/wiki/DI/en&quot;&gt;Wiren Board input reference&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;On ControlByWeb’s optically isolated digital inputs, an optocoupler keeps the external input voltage electrically separate from the module’s internal voltage. The DB-16P8R/DIN is one example of an opto-isolated board that supports both input modes. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-2/&quot;&gt;ControlByWeb digital input manual&lt;/a&gt; · &lt;a href=&quot;https://www.icpdas.com/en/product/DB-16P8R_DIN&quot;&gt;ICP DAS DIN relay board specifications&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Identify the input mode and terminals&lt;/h2&gt;
&lt;ol&gt;
&lt;li&gt;&lt;strong&gt;Identify the signal.&lt;/strong&gt; A bare pushbutton, reed switch or isolated relay contact can provide a dry closure. A powered DC sensor with an NPN or PNP output needs a compatible input circuit. &lt;a href=&quot;https://wiki.wirenboard.com/wiki/DI/en&quot;&gt;Wiren Board input reference&lt;/a&gt; · &lt;a href=&quot;https://library.automationdirect.com/3-wire-sinking-sourcing-devices-plc-input-modules/&quot;&gt;AutomationDirect sensor wiring&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Find the input channel and its return.&lt;/strong&gt; On the Waveshare Modbus RTU Module (A), &lt;code&gt;DI1&lt;/code&gt; and &lt;code&gt;DI2&lt;/code&gt; are inputs, &lt;code&gt;DGND&lt;/code&gt; is digital ground, and &lt;code&gt;DI COM&lt;/code&gt; is their common. The separate &lt;code&gt;CH1 COM&lt;/code&gt; and &lt;code&gt;CH2 COM&lt;/code&gt; belong to the relay outputs. &lt;a href=&quot;https://docs.waveshare.com/Modbus_RTU_Module_A#product-wiring-table&quot;&gt;Waveshare terminal table&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Check how the board selects dry or wet operation.&lt;/strong&gt; The ICP DAS DB-16P8R/DIN uses a jumper. On the Waveshare module, &lt;code&gt;DI COM&lt;/code&gt; wiring selects the mode. Leave that terminal open for dry-contact operation. &lt;a href=&quot;https://www.icpdas.com/en/product/DB-16P8R_DIN&quot;&gt;ICP DAS board specifications&lt;/a&gt; · &lt;a href=&quot;https://docs.waveshare.com/Modbus_RTU_Module_A#di-com-terminal&quot;&gt;Waveshare input common instructions&lt;/a&gt;&lt;/li&gt;
&lt;/ol&gt;
&lt;h2&gt;Wire a dry switch&lt;/h2&gt;
&lt;p&gt;Disconnect power before wiring. On a Wiren Board WB-MR6F DIN relay module, connect one wire of a momentary pushbutton to input 1 and the other to &lt;code&gt;iGND&lt;/code&gt;. The pushbutton closes the module’s sensing circuit. &lt;a href=&quot;https://docs.waveshare.com/Modbus_RTU_Module_A#5-power-off-operation&quot;&gt;Waveshare wiring precautions&lt;/a&gt; · &lt;a href=&quot;https://wiki.wirenboard.com/wiki/WB-MR6F_Modbus_Relay_Module/en#Inputs&quot;&gt;Wiren Board WB-MR6F input wiring&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;After powering up, open the Wiren Board web interface and watch the &lt;code&gt;Input1&lt;/code&gt; checkbox for the configured module. Press the button to close the contact, then release it. The input should show on when closed and off when open. &lt;a href=&quot;https://wiki.wirenboard.com/wiki/WB-MR6F_Modbus_Relay_Module/en&quot;&gt;Wiren Board WB-MR6F status display&lt;/a&gt; · &lt;a href=&quot;https://wiki.wirenboard.com/wiki/DI/en&quot;&gt;Wiren Board input states&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Wire a powered NPN or PNP sensor&lt;/h2&gt;
&lt;p&gt;For the Waveshare Modbus RTU Module (A), the published wet-contact range is &lt;strong&gt;5 to 36 V DC&lt;/strong&gt;. Disconnect power before wiring. For a three-wire DC sensor, connect its power leads to their respective supply terminals and follow the row for its output type. &lt;a href=&quot;https://docs.waveshare.com/Modbus_RTU_Module_A&quot;&gt;Waveshare hardware documentation&lt;/a&gt; · &lt;a href=&quot;https://library.automationdirect.com/3-wire-sinking-sourcing-devices-plc-input-modules/&quot;&gt;AutomationDirect three-wire sensor wiring&lt;/a&gt;&lt;/p&gt;
&lt;table&gt;
&lt;thead&gt;
&lt;tr&gt;
&lt;th&gt;Sensor output&lt;/th&gt;
&lt;th&gt;Connect &lt;code&gt;DI COM&lt;/code&gt; to&lt;/th&gt;
&lt;th&gt;Connect &lt;code&gt;DI1&lt;/code&gt; to&lt;/th&gt;
&lt;th&gt;Active signal&lt;/th&gt;
&lt;/tr&gt;
&lt;/thead&gt;
&lt;tbody&gt;
&lt;tr&gt;
&lt;td&gt;NPN (sinking)&lt;/td&gt;
&lt;td&gt;Sensor supply positive&lt;/td&gt;
&lt;td&gt;Sensor signal output&lt;/td&gt;
&lt;td&gt;Low&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;PNP (sourcing)&lt;/td&gt;
&lt;td&gt;Sensor supply negative&lt;/td&gt;
&lt;td&gt;Sensor signal output&lt;/td&gt;
&lt;td&gt;High&lt;/td&gt;
&lt;/tr&gt;
&lt;/tbody&gt;
&lt;/table&gt;
&lt;p&gt;Use one polarity for the input channels that share &lt;code&gt;DI COM&lt;/code&gt;. Once powered, change the sensor state and confirm the corresponding digital input value changes in Modbus Poll. &lt;a href=&quot;https://docs.waveshare.com/Modbus_RTU_Module_A#di-com-terminal&quot;&gt;Waveshare input common instructions&lt;/a&gt; · &lt;a href=&quot;https://library.automationdirect.com/3-wire-sinking-sourcing-devices-plc-input-modules/&quot;&gt;AutomationDirect shared-common guidance&lt;/a&gt; · &lt;a href=&quot;https://docs.waveshare.com/Modbus_RTU_Module_A/SW-Test#digital-input&quot;&gt;Waveshare input readback&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Use a dry switch with a voltage-sensing input&lt;/h2&gt;
&lt;p&gt;A dry switch can also switch a sensing supply in series. In Sealevel’s SeaI/O-430 example, connect the sensing supply positive to &lt;code&gt;C&lt;/code&gt; for the first input bank. Connect one switch terminal to input 1 and the other switch terminal to the sensing supply negative. The SeaI/O-430E specifies &lt;strong&gt;5 to 30 V DC&lt;/strong&gt; at its isolated inputs. &lt;a href=&quot;https://www.sealevel.com/how-should-i-connect-an-optically-isolated-input-and-voltage-supply-to-a-dry-contact-output&quot;&gt;Sealevel wiring example&lt;/a&gt; · &lt;a href=&quot;https://www.sealevel.com/seai-o-430e/&quot;&gt;SeaI/O-430E specifications&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;&lt;strong&gt;Evidence and limits.&lt;/strong&gt; Wiring and ratings were drawn from the manufacturer documentation for the models shown, including Waveshare SKU 34740 and Wiren Board WB-MR6F documentation revision 36312, checked November 26, 2026. The wiring steps were not performed.&lt;/p&gt;
</content:encoded><category>din-rail</category><category>dry-contact</category><category>wet-contact</category><category>digital-inputs</category><category>optocouplers</category><author>DIN Relay Guide Editorial</author></item><item><title>KinCony KC868 vs Waveshare ESP32-S3 vs smartDEN Relays</title><link>https://dinrelayguide.com/posts/kincony-kc868-waveshare-esp32-s3-denkovi-smartden-relay/</link><guid isPermaLink="true">https://dinrelayguide.com/posts/kincony-kc868-waveshare-esp32-s3-denkovi-smartden-relay/</guid><description>Compare KinCony, Waveshare, and Denkovi relay modules by channel count, contact type, power supply, and support for ESPHome, Wi-Fi, or MQTT.</description><pubDate>Thu, 26 Nov 2026 00:00:00 GMT</pubDate><content:encoded>&lt;p&gt;Choose the &lt;strong&gt;KinCony KC868-E16S&lt;/strong&gt; for an ESPHome project that needs wired Ethernet, dry-contact and analog inputs, and 16 replaceable relays. Choose the &lt;strong&gt;Waveshare ESP32-S3-Relay-6CH&lt;/strong&gt; for six Wi-Fi-controlled outputs with normally open and normally closed contacts. Choose the &lt;strong&gt;Denkovi smartDEN IP-16R-MQ&lt;/strong&gt; for 16 outputs with MQTT over Ethernet and built-in browser control. &lt;a href=&quot;https://www.kincony.com/kc868-e16s-hardware-design-details.html&quot;&gt;KinCony hardware&lt;/a&gt; · &lt;a href=&quot;https://www.kincony.com/forum/showthread.php?tid=2125&quot;&gt;KinCony ESPHome example&lt;/a&gt; · &lt;a href=&quot;https://docs.waveshare.com/ESP32-S3-Relay-6CH&quot;&gt;Waveshare documentation&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-iot-mqtt-ethernet-16-relay-module-din-rail-box&quot;&gt;Denkovi module&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Published specs by model&lt;/h2&gt;
&lt;p&gt;NO means normally open and NC means normally closed. &lt;a href=&quot;https://docs.waveshare.com/ESP32-S3-Relay-6CH#specifications&quot;&gt;Waveshare contact specifications&lt;/a&gt;&lt;/p&gt;
&lt;table&gt;
&lt;thead&gt;
&lt;tr&gt;
&lt;th&gt;Model&lt;/th&gt;
&lt;th&gt;Relay outputs&lt;/th&gt;
&lt;th&gt;Network and other interfaces&lt;/th&gt;
&lt;th&gt;Module power and mounting&lt;/th&gt;
&lt;th&gt;Vendor documentation&lt;/th&gt;
&lt;/tr&gt;
&lt;/thead&gt;
&lt;tbody&gt;
&lt;tr&gt;
&lt;td&gt;KinCony KC868-E16S&lt;/td&gt;
&lt;td&gt;16 replaceable relays, NO and COM terminals&lt;/td&gt;
&lt;td&gt;Ethernet, Wi-Fi, RS485. Also has 16 dry-contact inputs and 4 analog inputs.&lt;/td&gt;
&lt;td&gt;12 V DC in KinCony&apos;s hardware guide. Plastic housing for DIN-rail mounting.&lt;/td&gt;
&lt;td&gt;&lt;a href=&quot;https://www.kincony.com/kc868-e16s-hardware-design-details.html&quot;&gt;Hardware details&lt;/a&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;Waveshare ESP32-S3-Relay-6CH&lt;/td&gt;
&lt;td&gt;6 relays, one NO and one NC contact per channel&lt;/td&gt;
&lt;td&gt;2.4 GHz Wi-Fi, Bluetooth LE, isolated RS485&lt;/td&gt;
&lt;td&gt;7–36 V DC at the screw terminal or 5 V/1 A via USB-C. Rail-mount enclosure.&lt;/td&gt;
&lt;td&gt;&lt;a href=&quot;https://docs.waveshare.com/ESP32-S3-Relay-6CH&quot;&gt;Board specifications&lt;/a&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;Denkovi smartDEN IP-16R-MQ, DIN-rail box&lt;/td&gt;
&lt;td&gt;16 SPDT relays with NO and NC contacts&lt;/td&gt;
&lt;td&gt;Ethernet&lt;/td&gt;
&lt;td&gt;12 V DC or 24 V DC version, each with a ±2 V tolerance. DIN-rail box.&lt;/td&gt;
&lt;td&gt;&lt;a href=&quot;https://denkovi.com/smartden-iot-mqtt-ethernet-16-relay-module-din-rail-box&quot;&gt;Module specifications&lt;/a&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;/tbody&gt;
&lt;/table&gt;
&lt;h2&gt;Choose the control method&lt;/h2&gt;
&lt;ul&gt;
&lt;li&gt;&lt;strong&gt;KinCony for ESPHome.&lt;/strong&gt; KinCony documents ESPHome for Home Assistant. Its ESPHome example configures the wired Ethernet interface and maps the relays to switches. &lt;a href=&quot;https://www.kincony.com/forum/showthread.php?tid=2125&quot;&gt;KinCony ESPHome example&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Waveshare for programmable Wi-Fi control.&lt;/strong&gt; The Arduino example &lt;code&gt;02_MAIN_WIFI_STA&lt;/code&gt; requires changing the Wi-Fi configuration and serves a relay control page for devices on the same network. Turn off mobile data when using a phone to control the board. The separate MQTT example targets Waveshare Cloud, which Waveshare says is no longer maintained. &lt;a href=&quot;https://docs.waveshare.com/ESP32-S3-Relay-6CH/Arduino#example&quot;&gt;Waveshare Arduino examples&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Denkovi for an Ethernet protocol you already use.&lt;/strong&gt; The IP-16R-MQ has a built-in web interface, MQTT, and an HTTP API that returns XML or JSON. Choose IP-16R-MQ for MQTT, IP-16R-MT for Modbus TCP, or IP-16R for SNMP. &lt;a href=&quot;https://denkovi.com/smartden-iot-mqtt-ethernet-16-relay-module-din-rail-box&quot;&gt;Denkovi MQTT module&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/comparison-between-smartden-ip-modules&quot;&gt;Denkovi protocol comparison&lt;/a&gt;&lt;/li&gt;
&lt;/ul&gt;
&lt;h2&gt;Apply the specs to a project&lt;/h2&gt;
&lt;p&gt;Suppose a panel needs eight relay outputs, at least one NC contact, Ethernet MQTT control, and a 24 V DC module supply. The six-channel Waveshare board falls short on output count. The KC868-E16S meets the count but exposes NO and COM at its relay terminals. &lt;a href=&quot;https://docs.waveshare.com/ESP32-S3-Relay-6CH#specifications&quot;&gt;Waveshare specifications&lt;/a&gt; · &lt;a href=&quot;https://www.kincony.com/kc868-e16s-hardware-design-details.html&quot;&gt;KinCony relay terminals&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;The &lt;strong&gt;24 V DC smartDEN IP-16R-MQ DIN-rail version&lt;/strong&gt; meets those requirements. Before ordering for a DC load, confirm which relay part will be fitted. Denkovi lists two possible relay parts depending on stock, with different DC contact ratings. &lt;a href=&quot;https://denkovi.com/smartden-iot-mqtt-ethernet-16-relay-module-din-rail-box&quot;&gt;Denkovi technical parameters&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;&lt;strong&gt;Evidence and limits.&lt;/strong&gt; Vendor specifications and the KinCony ESPHome and Waveshare Arduino examples were checked on November 26, 2026. Denkovi lists firmware 1.22 for the IP-16R-MQ. This comparison is not based on hands-on testing. &lt;a href=&quot;https://denkovi.com/smartden-iot-mqtt-ethernet-16-relay-module-din-rail-box&quot;&gt;Denkovi firmware listing&lt;/a&gt;&lt;/p&gt;
</content:encoded><category>din-rail</category><category>relay-boards</category><category>esp32</category><category>mqtt</category><author>DIN Relay Guide Editorial</author></item><item><title>Best PoE &amp; Ethernet DIN-Rail Relays for Home Assistant</title><link>https://dinrelayguide.com/posts/best-poe-ethernet-din-rail-relay-controllers-home/</link><guid isPermaLink="true">https://dinrelayguide.com/posts/best-poe-ethernet-din-rail-relay-controllers-home/</guid><description>Compare the PoE-powered Atios SmartCore with two wired Shelly relays for Home Assistant. Match power, contacts and metering, then add your relay.</description><pubDate>Thu, 26 Nov 2026 00:00:00 GMT</pubDate><content:encoded>&lt;p&gt;Choose the &lt;strong&gt;Atios SmartCore&lt;/strong&gt; if you want a DIN-rail relay controller powered by its Ethernet cable. If you have AC power at the panel, choose the &lt;strong&gt;Shelly Pro 3&lt;/strong&gt; for dry contacts or the &lt;strong&gt;Shelly Pro 4PM V2&lt;/strong&gt; for metered AC outputs. &lt;a href=&quot;https://docs.atios.ch/smartcore/reference/datasheet&quot;&gt;Atios datasheet&lt;/a&gt; · &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-3-v1&quot;&gt;Pro 3 specifications&lt;/a&gt; · &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-4pm-v2&quot;&gt;Pro 4PM V2 specifications&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Compare power, contacts and control&lt;/h2&gt;
&lt;table&gt;
&lt;thead&gt;
&lt;tr&gt;
&lt;th&gt;Controller&lt;/th&gt;
&lt;th&gt;Controller power for a wired setup&lt;/th&gt;
&lt;th&gt;Relay outputs&lt;/th&gt;
&lt;th&gt;Home Assistant integration&lt;/th&gt;
&lt;/tr&gt;
&lt;/thead&gt;
&lt;tbody&gt;
&lt;tr&gt;
&lt;td&gt;&lt;a href=&quot;https://docs.atios.ch/smartcore/reference/datasheet&quot;&gt;Atios SmartCore ADE-R12-2.0&lt;/a&gt;&lt;/td&gt;
&lt;td&gt;802.3af PoE or external 20–30 V DC&lt;/td&gt;
&lt;td&gt;12 bistable dry contacts (16 A, 250 V AC)&lt;/td&gt;
&lt;td&gt;&lt;a href=&quot;https://docs.atios.ch/smartcore/matter/pairing-guide&quot;&gt;Matter&lt;/a&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;&lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-3-v1&quot;&gt;Shelly Pro 3&lt;/a&gt;&lt;/td&gt;
&lt;td&gt;110–240 V AC at the power terminals, with Ethernet for data&lt;/td&gt;
&lt;td&gt;3 dry contacts, with published switching limits of 16 A per channel and 48 A total&lt;/td&gt;
&lt;td&gt;&lt;a href=&quot;https://www.home-assistant.io/integrations/shelly&quot;&gt;Shelly&lt;/a&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;&lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-4pm-v2&quot;&gt;Shelly Pro 4PM V2&lt;/a&gt;&lt;/td&gt;
&lt;td&gt;110–240 V AC at the power terminals, with Ethernet for data&lt;/td&gt;
&lt;td&gt;4 &lt;a href=&quot;https://shelly-api-docs.shelly.cloud/gen2/Devices/Gen2/ShellyPro4PM/&quot;&gt;metered&lt;/a&gt; AC outputs, with published switching limits of 16 A per channel and 40 A total&lt;/td&gt;
&lt;td&gt;&lt;a href=&quot;https://www.home-assistant.io/integrations/shelly&quot;&gt;Shelly&lt;/a&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;/tbody&gt;
&lt;/table&gt;
&lt;p&gt;&lt;strong&gt;For PoE, plan two power paths.&lt;/strong&gt; Run the Ethernet cable from an 802.3af PoE switch port to the SmartCore&apos;s LAN port. Choose either PoE or the external DC input. The dry contacts switch power from the load supply. &lt;a href=&quot;https://docs.atios.ch/smartcore/reference/datasheet&quot;&gt;Atios datasheet&lt;/a&gt; · &lt;a href=&quot;https://docs.atios.ch/smartcore/getting-started/wiring&quot;&gt;SmartCore wiring guide&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;&lt;strong&gt;For Ethernet with AC power, match the outputs to the job.&lt;/strong&gt; The Pro 3 has separate load inputs and outputs for each of its three dry-contact relays. The Pro 4PM measures power and energy separately on each channel. &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-3-v1&quot;&gt;Pro 3 specifications&lt;/a&gt; · &lt;a href=&quot;https://shelly-api-docs.shelly.cloud/gen2/Devices/Gen2/ShellyPro4PM/&quot;&gt;Pro 4PM metering documentation&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;Before ordering, count your loads, match their voltage, current and load type to the model&apos;s specifications, and check the mounting dimensions. The SmartCore takes up 10 DIN modules. Use the wiring instructions for your exact model. For DALI lighting on the SmartCore, use the separate commissioning guide. &lt;a href=&quot;https://docs.atios.ch/smartcore/reference/datasheet&quot;&gt;Atios datasheet&lt;/a&gt; · &lt;a href=&quot;https://docs.atios.ch/smartcore/getting-started/wiring&quot;&gt;SmartCore wiring guide&lt;/a&gt; · &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-3-v1&quot;&gt;Pro 3 specifications&lt;/a&gt; · &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-4pm-v2&quot;&gt;Pro 4PM V2 specifications&lt;/a&gt; · &lt;a href=&quot;https://docs.atios.ch/smartcore/dali/dali-configurator&quot;&gt;DALI commissioning guide&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Add an Atios relay to Home Assistant over Matter&lt;/h2&gt;
&lt;p&gt;For a non-lighting on/off load already connected to &lt;strong&gt;Output 01&lt;/strong&gt;, map that output to a &lt;strong&gt;Switch&lt;/strong&gt; accessory before pairing. Atios ships the SmartCore with each digital input mapped to the matching output, so check the existing mapping for your circuit. &lt;a href=&quot;https://docs.atios.ch/smartcore/reference/quick-start&quot;&gt;SmartCore quick start&lt;/a&gt; · &lt;a href=&quot;https://docs.atios.ch/smartcore/accessory-manager/&quot;&gt;Accessory Manager&lt;/a&gt;&lt;/p&gt;
&lt;ol&gt;
&lt;li&gt;At &lt;code&gt;setup.atios.ch&lt;/code&gt;, select your SmartCore and click &lt;strong&gt;Connect&lt;/strong&gt;. In &lt;strong&gt;Accessory Manager&lt;/strong&gt;, select &lt;strong&gt;+&lt;/strong&gt; and choose &lt;strong&gt;Switch&lt;/strong&gt;. Give it a name, select &lt;strong&gt;Output 01&lt;/strong&gt;, then click &lt;strong&gt;Save Configuration&lt;/strong&gt; and reboot. &lt;a href=&quot;https://docs.atios.ch/smartcore/reference/quick-start&quot;&gt;SmartCore quick start&lt;/a&gt; · &lt;a href=&quot;https://docs.atios.ch/smartcore/accessory-manager/&quot;&gt;Accessory Manager&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;In &lt;strong&gt;System Settings&lt;/strong&gt;, enable &lt;strong&gt;Matter&lt;/strong&gt; and let the SmartCore reboot. The Matter pairing QR code is in &lt;strong&gt;System Settings&lt;/strong&gt;. &lt;a href=&quot;https://docs.atios.ch/smartcore/matter/pairing-guide&quot;&gt;Atios pairing guide&lt;/a&gt; · &lt;a href=&quot;https://docs.atios.ch/smartcore/reference/quick-start&quot;&gt;SmartCore quick start&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;On a regular Home Assistant OS setup that supports the official Matter Server app, open &lt;strong&gt;Settings &amp;gt; Devices &amp;amp; services&lt;/strong&gt; and add &lt;strong&gt;Matter&lt;/strong&gt;. Select &lt;strong&gt;Submit&lt;/strong&gt; when prompted for the connection method to install the official Matter Server app. &lt;a href=&quot;https://www.home-assistant.io/integrations/matter&quot;&gt;Home Assistant Matter integration&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;For a new device, open the current Companion app on an iPhone running iOS 16 or later with Bluetooth enabled. Go to &lt;strong&gt;Settings &amp;gt; Connectivity &amp;gt; Matter&lt;/strong&gt;, choose &lt;strong&gt;Add device&lt;/strong&gt;, then &lt;strong&gt;No. It’s new&lt;/strong&gt;. Scan the SmartCore QR code, tap &lt;strong&gt;Add to Home Assistant&lt;/strong&gt;, and follow the prompts. &lt;a href=&quot;https://www.home-assistant.io/integrations/matter&quot;&gt;Home Assistant Matter integration&lt;/a&gt;&lt;/li&gt;
&lt;/ol&gt;
&lt;h2&gt;Add either Shelly relay over Ethernet&lt;/h2&gt;
&lt;p&gt;Shelly requires the controller to be off when you connect or disconnect its LAN cable. Use a plug with nonmetallic surfaces wherever you touch it to plug or unplug the cable. &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-3-v1&quot;&gt;Pro 3 specifications&lt;/a&gt; · &lt;a href=&quot;https://kb.shelly.cloud/knowledge-base/shelly-pro-4pm-v2&quot;&gt;Pro 4PM V2 specifications&lt;/a&gt;&lt;/p&gt;
&lt;ol&gt;
&lt;li&gt;In Home Assistant, open &lt;strong&gt;Settings &amp;gt; Devices &amp;amp; services&lt;/strong&gt;. Set up the Shelly if it appears under &lt;strong&gt;Discovered&lt;/strong&gt;. &lt;a href=&quot;https://www.home-assistant.io/integrations/shelly&quot;&gt;Home Assistant Shelly integration&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;To add it manually, select &lt;strong&gt;Add Integration &amp;gt; Shelly&lt;/strong&gt;. Find the controller in your router and enter its hostname or IP address in &lt;strong&gt;Host&lt;/strong&gt;, then follow the prompts. &lt;a href=&quot;https://www.home-assistant.io/integrations/shelly&quot;&gt;Home Assistant Shelly integration&lt;/a&gt;&lt;/li&gt;
&lt;/ol&gt;
&lt;p&gt;The Shelly integration connects directly to the device and adds its relays as switch entities by default. &lt;a href=&quot;https://www.home-assistant.io/integrations/shelly&quot;&gt;Home Assistant Shelly integration&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;&lt;strong&gt;Evidence and limits.&lt;/strong&gt; The Atios ADE-R12-2.0 datasheet, Shelly Pro 3 and Pro 4PM V2 references, Shelly Gen2 API documentation, and Home Assistant integration guides were checked on November 26, 2026. The setup steps were not run on hardware.&lt;/p&gt;
</content:encoded><category>home-assistant</category><category>din-rail</category><category>poe</category><category>ethernet</category><category>relays</category><author>DIN Relay Guide Editorial</author></item><item><title>ControlByWeb X-410 vs Denkovi smartDEN for Modbus and MQTT</title><link>https://dinrelayguide.com/posts/controlbyweb-x-410-denkovi-smartden-local-modbus-mqtt/</link><guid isPermaLink="true">https://dinrelayguide.com/posts/controlbyweb-x-410-denkovi-smartden-local-modbus-mqtt/</guid><description>Compare the X-410 and smartDEN IP-Maxi for local Modbus TCP and MQTT panels, including relay contacts, power options, and the first relay command.</description><pubDate>Thu, 26 Nov 2026 00:00:00 GMT</pubDate><content:encoded>&lt;p&gt;Choose the ControlByWeb X-410 with MQTT-compatible firmware when one Ethernet module needs to offer both PLC access over Modbus TCP and MQTT access through a local broker. If you need eight changeover relays and one of those protocols, order the Denkovi smartDEN IP-Maxi-MT for Modbus TCP or the IP-Maxi-MQ for MQTT. &lt;a href=&quot;https://controlbyweb.com/x410/&quot;&gt;ControlByWeb X-410&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-ip-maxi-mt-modbus-tcp-io-relay-module-with-din-rail-box&quot;&gt;Denkovi IP-Maxi-MT&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-maxi-iot-io-relay-module-mqtt-http-din-rail-box&quot;&gt;Denkovi IP-Maxi-MQ&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Compare the panel hardware&lt;/h2&gt;
&lt;table&gt;
&lt;thead&gt;
&lt;tr&gt;
&lt;th&gt;Model&lt;/th&gt;
&lt;th&gt;PLC or broker protocol&lt;/th&gt;
&lt;th&gt;Built-in I/O&lt;/th&gt;
&lt;th&gt;Module power&lt;/th&gt;
&lt;/tr&gt;
&lt;/thead&gt;
&lt;tbody&gt;
&lt;tr&gt;
&lt;td&gt;&lt;a href=&quot;https://controlbyweb.com/x410/&quot;&gt;ControlByWeb X-410-I / X-410-E&lt;/a&gt;&lt;/td&gt;
&lt;td&gt;Modbus TCP and MQTT on compatible firmware&lt;/td&gt;
&lt;td&gt;4 SPST normally open relays with a shared common, 4 digital inputs, 1-Wire sensor support&lt;/td&gt;
&lt;td&gt;9–28 V DC, with PoE also available on the X-410-E&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;&lt;a href=&quot;https://denkovi.com/smartden-ip-maxi-mt-modbus-tcp-io-relay-module-with-din-rail-box&quot;&gt;Denkovi smartDEN IP-Maxi-MT&lt;/a&gt;&lt;/td&gt;
&lt;td&gt;Modbus TCP&lt;/td&gt;
&lt;td&gt;8 SPDT relays with normally open and normally closed contacts, 8 digital inputs, 4 analog inputs, 4 thermistor inputs, 2 analog outputs&lt;/td&gt;
&lt;td&gt;Order the 12 V DC or 24 V DC version&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;&lt;a href=&quot;https://denkovi.com/smartden-maxi-iot-io-relay-module-mqtt-http-din-rail-box&quot;&gt;Denkovi smartDEN IP-Maxi-MQ&lt;/a&gt;&lt;/td&gt;
&lt;td&gt;MQTT&lt;/td&gt;
&lt;td&gt;8 SPDT relays with normally open and normally closed contacts, 8 digital inputs, 4 analog inputs, 4 thermistor inputs, 2 analog outputs&lt;/td&gt;
&lt;td&gt;Order the 12 V DC or 24 V DC version&lt;/td&gt;
&lt;/tr&gt;
&lt;/tbody&gt;
&lt;/table&gt;
&lt;p&gt;All three mount on DIN rail. Before choosing the X-410, check whether the load circuits can safely share a common. ControlByWeb lists its contacts for general-purpose loads at a maximum of 1 A and 28 V AC or 24 V DC. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-2/&quot;&gt;ControlByWeb installation manual&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/x410/&quot;&gt;X-410 contact specifications&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-ip-maxi-mt-modbus-tcp-io-relay-module-with-din-rail-box&quot;&gt;IP-Maxi-MT enclosure&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-maxi-iot-io-relay-module-mqtt-http-din-rail-box&quot;&gt;IP-Maxi-MQ enclosure&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;For logic inside the panel, the X-410 has a Task Builder for conditional and scheduled actions. Both IP-Maxi variants document input-to-relay rules and a weekly schedule. &lt;a href=&quot;https://controlbyweb.com/x410/&quot;&gt;ControlByWeb Task Builder&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-ip-maxi-mt-modbus-tcp-io-relay-module-with-din-rail-box&quot;&gt;IP-Maxi-MT standalone mode&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-maxi-iot-io-relay-module-mqtt-http-din-rail-box&quot;&gt;IP-Maxi-MQ standalone mode&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Connect a local Modbus client&lt;/h2&gt;
&lt;p&gt;&lt;strong&gt;X-410.&lt;/strong&gt; In the setup pages, open &lt;strong&gt;General Settings → Advanced Network Settings&lt;/strong&gt; and set &lt;strong&gt;MODBUS (TCP/IP Slave)&lt;/strong&gt; to &lt;strong&gt;Yes&lt;/strong&gt;. Use the module’s LAN address and its &lt;strong&gt;Modbus Port&lt;/strong&gt;, which defaults to &lt;code&gt;502&lt;/code&gt;. ControlByWeb warns that enabling the device’s &lt;strong&gt;User&lt;/strong&gt; password disables Modbus. Modbus TCP provides no password protection. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-3/&quot;&gt;ControlByWeb setup manual&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/support/cbw-integration-manual/&quot;&gt;ControlByWeb Modbus manual&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;Open &lt;strong&gt;View Modbus Address Table&lt;/strong&gt; and look up the relay in the coil column. The address map can change as I/O is added or removed. For the manual’s Relay 1 example, the following entries use the same coil for the read and the write. Leave the load disconnected when trying the write. &lt;a href=&quot;https://controlbyweb.com/support/cbw-integration-manual/&quot;&gt;ControlByWeb address table and PLC examples&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/x410/&quot;&gt;ControlByWeb unloaded demo&lt;/a&gt;&lt;/p&gt;
&lt;table&gt;
&lt;thead&gt;
&lt;tr&gt;
&lt;th&gt;Operation&lt;/th&gt;
&lt;th&gt;Function-code addressing&lt;/th&gt;
&lt;th&gt;PLC coil address&lt;/th&gt;
&lt;/tr&gt;
&lt;/thead&gt;
&lt;tbody&gt;
&lt;tr&gt;
&lt;td&gt;Read Relay 1&lt;/td&gt;
&lt;td&gt;Read Coils (&lt;code&gt;01&lt;/code&gt;), address &lt;code&gt;0&lt;/code&gt;, quantity &lt;code&gt;1&lt;/code&gt;&lt;/td&gt;
&lt;td&gt;&lt;code&gt;1&lt;/code&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;Set Relay 1&lt;/td&gt;
&lt;td&gt;Write Single Coil (&lt;code&gt;05&lt;/code&gt;), address &lt;code&gt;0&lt;/code&gt;, desired on or off state&lt;/td&gt;
&lt;td&gt;&lt;code&gt;1&lt;/code&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;/tbody&gt;
&lt;/table&gt;
&lt;p&gt;&lt;strong&gt;IP-Maxi-MT.&lt;/strong&gt; Denkovi shows a Modbus Poll example on the product page. If Home Assistant is your client, open the vendor’s &lt;code&gt;HA.smartDEN IP-Maxi - Modbus.TCP&lt;/code&gt; example and replace its example IP address and port with those of your module. &lt;a href=&quot;https://denkovi.com/smartden-ip-maxi-mt-modbus-tcp-io-relay-module-with-din-rail-box&quot;&gt;Denkovi Modbus Poll example&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/home-assistant-and-denkovi-modules&quot;&gt;Denkovi Home Assistant application note&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Connect to a local MQTT broker&lt;/h2&gt;
&lt;p&gt;&lt;strong&gt;X-410.&lt;/strong&gt; Open &lt;strong&gt;General Settings → General Information → Firmware Revision&lt;/strong&gt;. ControlByWeb introduced MQTT 3.1.1 in 400 Series firmware &lt;strong&gt;v3.12&lt;/strong&gt;. Its release notes list 400 Series devices already on v3.0 or later as eligible for that update. ControlByWeb’s cloud service is optional. &lt;a href=&quot;https://controlbyweb.com/blog/firmware-v312-release-notes/&quot;&gt;ControlByWeb v3.12 release notes&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/support/manuals/x-400-users-manual/&quot;&gt;ControlByWeb 400 Series User’s Manual&lt;/a&gt;&lt;/p&gt;
&lt;ol&gt;
&lt;li&gt;In &lt;strong&gt;General Settings → MQTT&lt;/strong&gt;, add a broker and enter the local broker’s &lt;strong&gt;Hostname/IP&lt;/strong&gt; and &lt;strong&gt;Port&lt;/strong&gt;. Use standard MQTT mode for this example. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-3/&quot;&gt;ControlByWeb broker settings&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;Under &lt;strong&gt;Publish/Subscribe&lt;/strong&gt;, add a subscription. Select that broker and enter a command topic of your choice. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-3/&quot;&gt;ControlByWeb subscription settings&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;Add a publication for the same broker. Set &lt;strong&gt;Publish on Change&lt;/strong&gt; to &lt;strong&gt;Yes&lt;/strong&gt;, select Relay 2 and enter a separate status topic with the payload &lt;code&gt;${relay2}&lt;/code&gt;. Subscribe to the status topic from your MQTT client. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-3/&quot;&gt;ControlByWeb publication settings&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/support/cbw-integration-manual/&quot;&gt;ControlByWeb MQTT payload tokens&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;Start with Relay 2 off and the load disconnected. From the client, publish &lt;code&gt;relay2=1&lt;/code&gt; to the command topic. Check the status topic for the change to on. &lt;a href=&quot;https://controlbyweb.com/support/manuals/section-3/&quot;&gt;ControlByWeb subscription example&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/x410/&quot;&gt;ControlByWeb unloaded demo&lt;/a&gt;&lt;/li&gt;
&lt;/ol&gt;
&lt;p&gt;&lt;strong&gt;IP-Maxi-MQ.&lt;/strong&gt; Denkovi gives &lt;code&gt;SmartDEN_MQTTMaxi/E8EADA123456/Set/RS1&lt;/code&gt; as an example relay command topic. With the load disconnected, publish &lt;code&gt;0&lt;/code&gt; or &lt;code&gt;1&lt;/code&gt; to your module’s relay command topic for on/off control. &lt;a href=&quot;https://denkovi.com/smartden-maxi-iot-io-relay-module-mqtt-http-din-rail-box&quot;&gt;Denkovi MQTT connection and relay example&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;&lt;strong&gt;Evidence and limits.&lt;/strong&gt; Documentation was checked on November 26, 2026. The comparison uses ControlByWeb’s 400 Series User’s Manual v1.7 and v3.12 release notes, plus Denkovi’s IP-Maxi-MT and IP-Maxi-MQ pages, which list firmware 1.28. The examples were not run on hardware. &lt;a href=&quot;https://controlbyweb.com/support/manuals/x-400-users-manual/&quot;&gt;ControlByWeb manual&lt;/a&gt; · &lt;a href=&quot;https://controlbyweb.com/blog/firmware-v312-release-notes/&quot;&gt;ControlByWeb release notes&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-ip-maxi-mt-modbus-tcp-io-relay-module-with-din-rail-box&quot;&gt;Denkovi MT documentation&lt;/a&gt; · &lt;a href=&quot;https://denkovi.com/smartden-maxi-iot-io-relay-module-mqtt-http-din-rail-box&quot;&gt;Denkovi MQ documentation&lt;/a&gt;&lt;/p&gt;
</content:encoded><category>din rail</category><category>ethernet</category><category>modbus tcp</category><category>mqtt</category><category>relays</category><author>DIN Relay Guide Editorial</author></item><item><title>Sizing 24VDC Power Supplies &amp; Contactors for DIN-Rail Relays</title><link>https://dinrelayguide.com/posts/sizing-24vdc-power-supplies-contactors-multi-channel-din/</link><guid isPermaLink="true">https://dinrelayguide.com/posts/sizing-24vdc-power-supplies-contactors-multi-channel-din/</guid><description>Use an eight-channel DIN-rail relay example to size a 24VDC supply for holding and pickup current, check derating, and choose contactors.</description><pubDate>Thu, 26 Nov 2026 00:00:00 GMT</pubDate><content:encoded>&lt;p&gt;Size the 24 VDC supply for the largest steady load and the highest startup load when coils pull in together. Compare the holding load with the supply’s continuous rating at the enclosure temperature. If the supply has a peak rating, check that it covers the startup load for the time it lasts. Choose each contactor’s coil for the control circuit and its main poles for the load voltage, current and switching duty. &lt;a href=&quot;https://maplesystems.com/din-rail-power-supplies/?_series=economical-ultra-slim&quot;&gt;Power supply sizing&lt;/a&gt; · &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d09bd-contactor-tesys-deca-3p-3no-ac-3-3e-440v-9a-24v-dc-coil-screw-clamp-terminals/&quot;&gt;Example contactor ratings&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Calculate holding and pickup current&lt;/h2&gt;
&lt;p&gt;List the relay inputs, contactor coils and any controller, sensors or other equipment fed by the same 24 VDC supply. Use each device’s published maximum current where available. If a 24 VDC coil is specified in watts, divide those watts by 24 to estimate its current at nominal voltage. &lt;a href=&quot;https://maplesystems.com/din-rail-power-supplies/?_series=economical-ultra-slim&quot;&gt;Maple Systems sizing guide&lt;/a&gt;&lt;/p&gt;
&lt;ul&gt;
&lt;li&gt;&lt;strong&gt;Holding current.&lt;/strong&gt; Add the current of devices already powered and the hold-in current of every coil that can remain energized together.&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Pickup current.&lt;/strong&gt; For each possible start, add the current already on the supply and the inrush current of coils that can start together. Use hold-in current for coils already energized, and count each coil once.&lt;/li&gt;
&lt;/ul&gt;
&lt;h3&gt;Worked example for eight channels&lt;/h3&gt;
&lt;p&gt;Assume eight relay outputs each switch one Schneider Electric contactor coil from the same 24 VDC supply. All eight can stay on, and all eight can start together. Calculate the coil subtotals from the published contactor coil powers at 20 °C. &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d09bd-contactor-tesys-deca-3p-3no-ac-3-3e-440v-9a-24v-dc-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D09BD&lt;/a&gt; · &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d50abd-contactor-tesys-deca-3p-3-no-ac-3-ac-3e-400v-50a-24v-dc-standard-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D50ABD&lt;/a&gt;&lt;/p&gt;
&lt;table&gt;
&lt;thead&gt;
&lt;tr&gt;
&lt;th&gt;Load on the 24 VDC supply&lt;/th&gt;
&lt;th style=&quot;text-align:right&quot;&gt;All channels holding&lt;/th&gt;
&lt;th style=&quot;text-align:right&quot;&gt;All channels picking up&lt;/th&gt;
&lt;/tr&gt;
&lt;/thead&gt;
&lt;tbody&gt;
&lt;tr&gt;
&lt;td&gt;Relay inputs and other devices on the same supply&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;Add current in the holding case&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;Add current in the pickup case&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;4 LC1D09BD coils, 5.4 W each for hold-in and inrush (at 20 °C)&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;4 × 5.4 W ÷ 24 V = 0.900 A&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;4 × 5.4 W ÷ 24 V = 0.900 A&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;4 LC1D50ABD coils, 7.4 W holding and 19 W inrush each (at 20 °C)&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;4 × 7.4 W ÷ 24 V ≈ 1.233 A&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;4 × 19 W ÷ 24 V ≈ 3.167 A&lt;/td&gt;
&lt;/tr&gt;
&lt;tr&gt;
&lt;td&gt;&lt;strong&gt;Calculated contactor coil subtotal&lt;/strong&gt;&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;&lt;strong&gt;2.13 A&lt;/strong&gt;&lt;/td&gt;
&lt;td style=&quot;text-align:right&quot;&gt;&lt;strong&gt;4.07 A&lt;/strong&gt;&lt;/td&gt;
&lt;/tr&gt;
&lt;/tbody&gt;
&lt;/table&gt;
&lt;p&gt;In this example, consider one LC1D50ABD picking up while the other seven coils hold. Replace that coil’s holding current with its pickup current. The coil subtotal becomes 0.900 A + 1.233 A + (19 W − 7.4 W) ÷ 24 V ≈ &lt;strong&gt;2.62 A&lt;/strong&gt;. Use the simultaneous figure if the channels can start together at power-up.&lt;/p&gt;
&lt;h2&gt;Check continuous capacity and timed boost&lt;/h2&gt;
&lt;p&gt;Add the relay inputs and other 24 VDC loads to each coil subtotal before comparing the totals. Use the supply’s derating curve to find its continuous output at the worst-case enclosure temperature. The holding total must fit within that output. &lt;a href=&quot;https://maplesystems.com/din-rail-power-supplies/?_series=economical-ultra-slim&quot;&gt;Maple Systems sizing guide&lt;/a&gt;&lt;/p&gt;
&lt;p&gt;If the pickup total exceeds continuous output, check the supply’s peak current and the time it can sustain that current. Confirm that the supply is rated for the available AC input voltage. Maple Systems’ Economical models must cover the pickup total with their rated current. &lt;a href=&quot;https://maplesystems.com/din-rail-power-supplies/?_series=economical-ultra-slim&quot;&gt;Maple Systems sizing guide&lt;/a&gt;&lt;/p&gt;
&lt;h2&gt;Check coil current and suppression&lt;/h2&gt;
&lt;ul&gt;
&lt;li&gt;&lt;strong&gt;Coil current.&lt;/strong&gt; The example LC1D50ABD draws about 0.79 A at pickup and 0.31 A holding, calculated at 24 V from the 20 °C coil specs. &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d50abd-contactor-tesys-deca-3p-3-no-ac-3-ac-3e-400v-50a-24v-dc-standard-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D50ABD coil data&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Coil suppression.&lt;/strong&gt; Check whether the contactor coil has built-in suppression. Both example contactors list a built-in bidirectional diode suppressor. &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d09bd-contactor-tesys-deca-3p-3no-ac-3-3e-440v-9a-24v-dc-coil-screw-clamp-terminals/&quot;&gt;LC1D09BD coil data&lt;/a&gt; · &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d50abd-contactor-tesys-deca-3p-3-no-ac-3-ac-3e-400v-50a-24v-dc-standard-coil-screw-clamp-terminals/&quot;&gt;LC1D50ABD coil data&lt;/a&gt;&lt;/li&gt;
&lt;/ul&gt;
&lt;h2&gt;Select the contactor coil and main poles&lt;/h2&gt;
&lt;ul&gt;
&lt;li&gt;&lt;strong&gt;Coil.&lt;/strong&gt; Specify 24 VDC for this control supply. Check the control circuit voltage and use the exact coil variant’s inrush and hold-in data in the current budget. &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d09bd-contactor-tesys-deca-3p-3no-ac-3-3e-440v-9a-24v-dc-coil-screw-clamp-terminals/&quot;&gt;Example coil data&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Main poles.&lt;/strong&gt; Match the load’s voltage and current to the contactor’s rated operational voltage and current for the applicable utilization category. Check the pole arrangement under pole contact composition. Both example contactors have three normally open main poles. &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d09bd-contactor-tesys-deca-3p-3no-ac-3-3e-440v-9a-24v-dc-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D09BD&lt;/a&gt; · &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d50abd-contactor-tesys-deca-3p-3-no-ac-3-ac-3e-400v-50a-24v-dc-standard-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D50ABD&lt;/a&gt;&lt;/li&gt;
&lt;li&gt;&lt;strong&gt;Duty.&lt;/strong&gt; Check the selected model’s application and utilization category. Schneider lists the example contactors for motor control under AC-3/AC-3e. Check the maximum operating rate at the stated temperature. &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d09bd-contactor-tesys-deca-3p-3no-ac-3-3e-440v-9a-24v-dc-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D09BD&lt;/a&gt; · &lt;a href=&quot;https://shop.se.com/pro/ae/en/product/lc1d50abd-contactor-tesys-deca-3p-3-no-ac-3-ac-3e-400v-50a-24v-dc-standard-coil-screw-clamp-terminals/&quot;&gt;Schneider LC1D50ABD&lt;/a&gt;&lt;/li&gt;
&lt;/ul&gt;
&lt;p&gt;&lt;strong&gt;Evidence and limits.&lt;/strong&gt; The calculations are based on the linked product data and sizing guidance checked on November 26, 2026. This guide is not based on hands-on testing.&lt;/p&gt;
</content:encoded><category>24 vdc</category><category>power supplies</category><category>din-rail relays</category><category>contactors</category><author>DIN Relay Guide Editorial</author></item></channel></rss>